A high proportion of distributed generators (DGs) connected to the distribution network causes a significant change in the normal and fault currents of the system as well as in the linearization of the characteristics. It is difficult to adapt to conventional protection. This paper theoretically analyzes the possible impact of fault current characteristics on traditional protection based on single-ended informativeness after connecting to DGs. From the perspective of protection action, the evaluation index system of DG protection is established by considering the maximum short-circuit current output from DG. Combined with the relay protection requirements, the calculation method of evaluation indexes is given concerning the protection characteristics and expert experience. An analytic hierarchy process (AHP) and a CRITIC combination assignment method based on the principle of minimum information identification are proposed. The scores of different types of protection before and after DG access are calculated using the proposed methodology employing a typical distribution network example. The proposed method can quantitatively obtain the distribution network protection adaptability boundary. In the actual calculation example selected in this paper, a DG can reasonably improve the adaptability of the three-stage current protection when it increases the current amplitude at a penetration rate of 50%; the DG needs to adjust the three-stage current protection rectification value when it decreases the current amplitude at a penetration rate of 20%; and adaptive overcurrent protection and inverse time limit current protection need to be adjusted when the penetration rate of DG is 50%. Compared with the traditional protection evaluation method, the method adopted in this paper can intuitively derive the weak link between protection handling faults after DG access as well as the appropriate capacity of DG to improve protection performance. It can provide a powerful reference for the optimization of protection schemes after the high percentage of DG access.

Funder

North China Electric Power Research Institute Co., Ltd.

Publisher

MDPI AG

Reference36 articles.

1. Building a new power system with new energy as the main body in the 14th Five-Year Plan;Zhao;China Energy,2021

2. Centralized and Distributed Voltage Control: Impact on Distributed Generation Penetration;Vovos;IEEE Trans. Power Syst.,2007

3. Integration Issues of Distributed Generation in Distribution Grids;Coster;Proc. IEEE,2010

4. Hussain, B., Sharkh, S.M., and Abusara, M.A. (2010–1, January 29). Integration of distributed generation into the grid: Protection challenges and solutions. Proceedings of the 10th IET International Conference on Developments in Power System Protection (DPSP 2010). Managing the Change, Manchester, UK.

5. Adaptive overcurrent protection scheme for active distribution network with high penetration access of distributed generation and multiple loads;Wang;High Volt. Technol.,2019

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3