Abstract
Managing a large fleet of ageing assets has become a technical challenge faced by many electricity utilities in developed countries. Asset managers are increasingly interested in techniques that can help extend the useful lifetime of a transformer. Oil regeneration is one of such techniques. In this paper, oil regeneration experiments were performed on a 6.4/0.4 kV retired distribution transformer to investigate the effect of oil regeneration on improving paper conditions. Oil regeneration was conducted in two stages, with the first stage aimed at ‘cleaning the oil’ and the second stage targeted at ‘cleaning the paper’. Oil samples were collected at regular intervals throughout the process and paper samples were obtained from the transformer before and after each oil regeneration stage. It was found that oil regeneration restores oil parameters, including moisture and acidity, similar to those of new oils at the end of stage 1. Analysis of paper samples indicated a reduction in paper moisture at the end of stage 2 by nearly 40%, while low molecular weight acids (LMA) in paper exhibited a reduction by around 30% on average. It is found that the extended oil regeneration period, i.e., stage 2, is necessary to improve the paper condition and hence to reduce the paper ageing rate.
Funder
Electricity North West, United Kingdom
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous)
Cited by
13 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献