Abstract
The recently stipulated grid codes require wind generators to re-initiate normal power production after grid voltage sag. This paper presents a comparative performance of two commonly employed variable speed wind turbines in today’s electricity market, the doubly fed induction generator (DFIG) and the permanent magnet synchronous generator (PMSG) wind turbines. The evaluation of both wind turbines was performed for weak, normal and strong grids, considering the same machine ratings of the wind turbines. Because of the critical situations of the wind turbines during faulty conditions in the weak grids, an analysis was done considering the use of effective series dynamic braking resistor (SDBR) for both wind turbines. The grid voltage variable was employed as the signal for switching the SDBR in both wind turbines during transient state. Additionally, an overvoltage protection system was considered for both wind turbines using the DC chopper in the DC-link excitation circuitry of both wind turbines. Furthermore, a combination of the SDBR over-voltage protection scheme (OVPS) was employed in both wind turbines at weak grid condition in order to improve the performance of the variable speed wind turbines and keep the operation of the power converters within their permissible limits. Furthermore, the performance of the DFIG and PMSG wind turbines in weak grids were further investigated, considering the combination of 75% and 50% effectively sized SDBR and OVPS. It was observed that, even with a 50% reduction in SDBR or OVPS, the performance of both wind turbines is still satisfactory with faulty conditions. Therefore, it is recommended to use a combination of the SDBR and OVPS with DFIG- or PMSG-based variable speed wind turbines to achieve a superior fault ride through performance, especially in weak grids. The system performance was evaluated using the power system computer design and electromagnetic transient including DC (PSCAD/EMTDC) platform.
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous),Building and Construction
Reference48 articles.
1. Nduwamungu, A., Ntagwirumugara, E., Mulolani, F., and Bashir, W. (2020). Fault Ride through Capability Analysis (FRT) in Wind Power Plants with Doubly Fed Induction Generators for Smart Grid Technologies. Energies, 13.
2. Fault diagnosis of wind turbine with SCADA alarms based multidimensional information processing method;Qiu;Renew. Energy,2020
3. Okedu, K.E., Muyeen, S.M., Takahashi, R., and Tamura, J. (2011, January 20–23). Protection schemes for DFIG considering rotor current and DC-link voltage. Proceedings of the 24th IEEE-ICEMS (International Conference on Electrical Machines and System), Beijing, China.
4. Active Voltage Control for DFIG-Based Wind Farm Integrated Power System by Coordinating Active and Reactive Powers under Wind Speed Variations;Ouyang;IEEE Trans. Energy Convers.,2019
5. Enhanced performance of PMSG Wind Turbines during grid disturbance at different network strengths considering fault current limiter;Okedu;Int. Trans. Electr. Energy Syst.,2021
Cited by
3 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献