Abstract
A centralized multiple back-up protection scheme with sharing data between adjacent substations based on IEC 61850 is suggested in this paper to overcome the inherent defects of a conventional back-up protection scheme such as uncertainty of a remote end condition, especially for a distance relay, long operating time delay, and IED/CT fails. A current differential protection element, a distance-based directional protection element, local back-up, and remote back-up protection elements are applied for the multiple back-up protection scheme suggested in this paper. The phasor voltage/current data of the IMU are transferred to a CPCU. In this paper, the IMU has two functions, which are local protection IED and merging unit, as well. The CPCU performs the back-up protection functions by using the phasor voltage/current data collected from other CPCUs located at the adjacent substations. IMU/CT fails are also considered. To verify the back-up protection scheme proposed, a testbed was composed of IMUs (implemented with ADS8688 and TMDSIDK572X), grand-master-clocks (LANTIME M1000-IMS), network switches (Syn 1588 Gbit switch), RTDS, and CPCUs. A target power system was modelled with RSCAD. The results of this research can be expected to provide a practical guide to constructing the future centralized protection for a digital substation.
Funder
Korea Electric Power Corporation
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous),Building and Construction
Reference22 articles.
1. Centralized Substation Protection and Control;Das,2015
2. A new-style centralized IED based on IEC 61850;Yi;Proceedings of the IEEE Power and Energy Society General Meeting—Conversion and Delivery of Electrical Energy in the 21st Century,2008
3. A novel substation area backup protection for smart substation;Li;Proceedings of the 2013 IEEE PES Asia-Pacific Power and Energy Engineering Conference (APPEEC),2013
4. Communication Modeling for Differential Protection in IEC-61850-Based Substations
5. Principle and implementation of substation-area backup protection for digital substation;Gao;Proceedings of the 12th IET International Conference on Developments in Power System Protection (DPSP 2014),2014
Cited by
1 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献