Affiliation:
1. China Electric Power Research Institute, Wuhan 430074, China
Abstract
High-voltage switchgears can generate high-frequency and high-amplitude electromagnetic interference during their operation, which may lead to abnormal outputs of the measurement devices, thus giving rise to measurement errors or protective relay malfunctions and impacts on the stable running of the power grid. Considering the air breakdown delay, a dynamic reignition model consisting of the hyperbolic model, the static model and the improved Mayr model is proposed to analyze the transient process during the on/off operation of open-type disconnectors. Meanwhile, the influence of arc resistance, line length and breakdown delay on the model were analyzed, and an experimental circuit was built to verify the simulation results through a comparison. It was found that the proposed model could reflect the high-frequency voltage and current during the on/off operation more accurately and thus provide an effective method for the precise modeling of the switching operation of the disconnector.
Funder
Science and Technology Project of the State Grid Corporation of China
Subject
Management, Monitoring, Policy and Law,Renewable Energy, Sustainability and the Environment,Geography, Planning and Development,Building and Construction