Abstract
Fault detection and isolation are important tasks to improve the protection system of low voltage direct current (LVDC) networks. Nowadays, there are challenges related to the protection strategies in the LVDC systems. In this paper, two proposed methods for fault detection and isolation of the faulty segment through the line and bus voltage measurement were discussed. The impacts of grid fault current and the characteristics of protective devices under pre-fault normal, under-fault, and post-fault conditions were also discussed. It was found that within a short time after fault occurrence in the network, this fault was quickly detected and the faulty line segment was efficiently isolated from the grid, where this grid was restored to its normal operating conditions. For analysing the fault occurrence and its isolation, two algorithms with their corresponding MATLAB/SIMULINK platforms were developed. The findings of this paper showed that the proposed methods would be used for microgrid protection by successfully resolving the fault detection and grid restoration problems in the LVDC microgrids, especially in rural villages.
Funder
Resilient Electricity Networks for a productive Grid Architecture (RENGA) project based at the Imperial College of London
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous),Building and Construction
Cited by
9 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献