Abstract
This paper deals with the study of a non-destructive technique to detect the aging state of cable insulation used in a nuclear environment subjected to radiation and temperature aging. Cable samples were aged under dose rates ranging from 0.42 and 1.06 kGy/h at 55 and 85 °C. The imaginary part of the permittivity at 100 kHz is found to correlate well with mechanical properties, such as elongation at break, which is typically used to diagnose cable insulation, but it is a destructive property and cannot be used on field. It has been demonstrated also that a post-irradiation effect occurs even years after aging is stopped, increasing the imaginary permittivity and worsening mechanical properties due to the slow conversion of radicals into oxidized species. The main consequence is that when cable insulation is subjected to a nuclear accident, releasing a huge amount of radiation, the health of cable insulation must be followed also for a long time after the accident occurred, since aging due to oxidation progresses even when the radiation source is switched off.
Subject
Polymers and Plastics,General Chemistry
Reference29 articles.
1. Assessment and Management of Ageing of Major Nuclear Power plant Components Important to Safety,2011
2. Nuclear Power Plants—Instrumentation and Control Important to Safety—Electrical Equipment Condition Monitoring Methods—Part 3: Elongation at Break,2012
3. Assessing and Managing Cable Ageing in Nuclear Power Plants,2012
4. Effects of thermal ageing on mechanical and thermal behaviors of linear low density polyethylene pipe
Cited by
24 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献