Abstract
Dissatisfaction with indoor air quality is common even in relatively new or renovated Polish school buildings. To improve air quality in educational buildings, portable devices have seen increased use, for which manufacturers guarantee a high level of indoor air purification. However, their optimized operation largely depends on their correct use. The aim of this article was to determine the effectiveness of air purification in a primary school using an air purification device with an analysis of the classroom indoor air quality (IAQ). Two criteria were used, microbiological and particulate matter concentration. Measurements were made before device installation and during its continuous operation, and before and after lessons on chosen days. Measurements related to IAQ did not detect clear differences in the analyzed measurement periods. For microbiological contamination, in the morning before lessons, the total count for all bacteria and microscopic fungi was definitely lower than after lessons. Comparing the periods before and after device installation, no clear tendency for reducing the bacteria count or microscopic fungi occurred during air purifier operation, nor was there any noticeable trend in the reduction of particulate matter. There was no improvement in air quality in the classrooms during the operation of the purification devices.