Author:
Liu Yongxin,Song Bin,Wang Linong,Gao Jiachen,Xu Rihong
Abstract
The transformers work in a complex environment, which makes them prone to failure. Dissolved gas analysis (DGA) is one of the most important methods for oil-immersed transformers’ internal insulation fault diagnosis. In view of the high correlation of the same fault data of transformers, this paper proposes a new method for transformers’ fault diagnosis based on correlation coefficient density clustering, which uses density clustering to extrapolate the correlation coefficient of DGA data. Firstly, we calculated the correlation coefficient of dissolved gas content in the fault transformers oil and enlarged the correlation of the same fault category by introducing the amplification coefficient, and finally we used the density clustering method to cluster diagnosis. The experimental results show that the accuracy of clustering is improved by 32.7% compared with the direct clustering judgment without using correlation coefficient, which can effectively cluster different types of transformers fault modes. This method provides a new idea for transformers fault identification, and has practical application value.
Subject
Fluid Flow and Transfer Processes,Computer Science Applications,Process Chemistry and Technology,General Engineering,Instrumentation,General Materials Science
Cited by
31 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献