Author:
Sánchez-Barroso Gonzalo,García Sanz-Calcedo Justo
Abstract
Unidirectional flow air-conditioning systems are suitable for achieving indoor air quality required in high-performance operating rooms (organ transplants, cardiac surgery, aorta, orthopedic, burns, etc.). This paper analyzes indoor environmental conditions and technical and hygienic requirements for the design of heating, ventilation, and air-Conditioning (HVAC) systems for high-performance operating theatres. The main standards applicable to this type of operating rooms were compiled. Standard UNE 100713:2015, ASHRAE Standard 170-2017, and the European pre-norm EN 16244 were analyzed. A case study shows the lack of uniformity in design criteria and their ranges of values, which generates different design approaches. It was concluded that using these standards applicable to high-performance operating rooms leads to very different indoor environmental conditions for patients and medical personnel—air velocity profiles, air movement pattern, temperature, relative humidity gradients, and pressure stratification. Computational fluid dynamics (CFD) studies have been shown to detect areas of haven that favor microbiological load accumulation. In this way, it is possible to define cleaning protocols to attend these anomalies in a preventive way.
Subject
Management, Monitoring, Policy and Law,Renewable Energy, Sustainability and the Environment,Geography, Planning and Development
Reference59 articles.
1. Reducing risk of surgery;Memarzadeh;ASHRAE J.,2003
2. The importance of airborne bacterial contamination of wounds
3. Airborne contamination of wounds in joint replacement operations: the relationship to sepsis rates
4. Comparison of operating room ventilation systems in the protection of the surgical site;Memarzadeh;ASHRAE Trans.,2002
5. Assessment of Thermal Comfort during Surgical Operations;Mora;ASHRAE Trans.,2001
Cited by
29 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献