Author:
Ji Liang,Cao Zhe,Hong Qiteng,Chang Xiao,Fu Yang,Shi Jiabing,Mi Yang,Li Zhenkun
Abstract
This paper presents an improved inverse-time over-current protection method based on the compound fault acceleration factor and the beetle antennae search (BAS) optimization method for a microgrid. The proposed method can not only significantly increase the operation speed of the inverse-time over-current protection but also improve the protection coordination by considering the possible influential factors in terms of microgrid operation modes, distributed generation (DG) integration status, fault types, and positions, which are marked as the most challenging problems for over-current protection of a microgrid. In this paper, a new Time Dial Setting (TDS) of inverse-time protection is developed by applying a compound fault acceleration factor, which can notably accelerate the speed of protection by using low-voltage and short-circuit impedance during the fault. In order to improve the protection coordination, the BAS algorithm is then used to optimize the protection parameters of the pick-up current, TDS, and the inverse time curve shape coefficient. Finally, case studies and various evaluations based on DIgSILENT/Power Factory are carried out to illustrate the effectiveness of the proposed method.
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous)
Cited by
16 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献