Abstract
In this article, we presented the results of the tests performed on three sets of samples of glass-reinforced epoxy (GRE) core rods used in alternating current (AC) composite insulators with silicone rubber housing. The objective of this examination was to test the aging resistance of the rod material when exposed to direct current (DC) high voltage. We hypothesized that the long-term effects of the electrostatic field on the GRE core rod material would lead to a gradual degradation of its mechanical properties caused by ionic current flow. Further, we hypothesized that reducing the mechanical strength of the GRE core rod would lead to the breakage of the insulator. The first group of samples was used for reference. The samples from the second group were subjected to a temperature of about 50 °C for 6000 h. The third group of samples were aged by temperature and DC high voltage for the same time. The samples were examined using the 3-point bending test, micro-hardness measurement and microscopic analysis. No recordable degradation effects were found. Long-term temperature impact and, above all, the combined action of temperature and DC high voltage did not reduce the mechanical parameters or change the microstructure of the GRE material.
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous)
Reference13 articles.
1. High-Voltage DC Power Transmission: Should HVDC Replace AC in Power Systems?https://www.allaboutcircuits.com/technical-articles/high-voltage-dc-power-transmission-hvdc-replace-ac-power-systems/
2. Surface Charge & DC Flashover Performance of Composite Insulatorshttps://www.inmr.com/surface-charge-flashover-performance-composite-insulators/
Cited by
4 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献