Abstract
In this paper, a weighted least square (WLS) state estimation algorithm with equality constraints is proposed for smart distribution networks embedded with microgrids. Since only a limited number of real-time measurements are available at the primary or secondary substations and distributed generation sites, load estimates at unmeasured buses remote from the substations are needed to execute state estimation. The load information can be obtained by forecasted and historical data or smart real-time meters. The proposed algorithms can be applied in either grid-connected or islanded operation mode and can efficiently identify breaker status errors at the main substations and feeders, where sufficient measurement redundancy exists. The impact of the accuracy of real and pseudo-measurements on the estimated bus voltages is tested with a 55-bus distribution network including distributed generation.
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous)
Cited by
14 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献