About ten hydroelectric power plants realized from 1970 to 1990 in Romania are confronted with stator overheating. The developed mathematical model analyzes the voltage stability based on modal analysis of the Jacobian matrix, identifying the hazardous modes of variation between voltage and flow rate, correlated with the characteristics of the analyzed generators and their response to these variations. Vulnerable elements in the system for inductive and capacitive modes of operation are identified. In these conditions, hydro generators cannot attend the secondary voltage control, not even for a frequency power dependency control. The elaborated mathematical model was tested at the hydroelectric power plants Gilceag, Mariselu, and Susag with similar functioning conditions. The necessary conditions for stator ventilation and variation of flow hydrodynamic parameters during the operation were established. The theoretical model was tested with an experimental method applied separately for the thermal and ventilation conditions. Some results obtained during the measurements are illustrated and correlated with the theoretical results. The model was tested to prevent the onset instability of voltage drops and accelerated overheating. Finally, some solutions to minimize the stators overheating based on local conditions are recommended.
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous)
Reference31 articles.
1. Centrale, Statii si Retele Electrice;Guzun,2017
2. Hidrocentrale in Caverne, Baraje Imense, Galerii Subterane: Realizarile Comuniste la Amenajarea Hidroenergetica de pe Valea Sebesuluihttps://adevarul.ro/locale/alba-iulia/hidrocentrale-caverne-barajeimense-galerii-subterane-realizarile-comuniste-amenajareahidroenergetica-valea-sebesului
3. Echipamente Pentru Realizarea Reglajului Frecventa-Putere 2008http://www.transelectrica.ro/
4. Causes of the 2003 Major Grid Blackouts in North America and Europe, and Recommended Means to Improve System Dynamic Performance
5. Power System Stability and Control;Kundur,2017
Cited by
1 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献