Affiliation:
1. Key Laboratory of Modern Power System Simulation and Control and Renewable Energy Technology, Ministry of Education, School of Electrical Engineering, Northeast Electric Power University, Jilin City 132012, China
Abstract
Under atmospheric pressure, partial discharge initiated by free metallic particles has consistently been a significant factor leading to failures in high-voltage electrical equipment. Simulating the propagation of negative streamer discharge in N2/O2 mixtures contributes to a better understanding of the occurrence and evolution of partial discharge, optimizing the insulation performance of electrical equipment. In this study, a two-dimensional plasma fluid dynamics model coupled with the current module was employed to simulate the evolution process of negative streamer discharge caused by one free metallic particle under a suspended potential at 220 kV applied voltage conditions. Simulation results indicated that the discharge process could be divided into two distinct stages: In the first stage, the electron ionization region detached from the electrode surface and propagated independently. During this stage, the corona discharge on the negative electrode surface provided seed electrons crucial for the subsequent development of negative corona discharge. The applied electric field played a dominant role in the propagation of the electron region, especially in the electron avalanche region. In the second stage, space charge gradually took over, causing distortion in the spatial field, particularly generating a substantial electric field gradient near the negative electrode surface, forming an ionization pattern dominated by ionization near the negative electrode surface. These simulation results contribute to a comprehensive understanding of the complex dynamic process of negative streamer discharge initiated by free metallic particles, providing essential insights for optimizing the design of electrical equipment and insulation systems.
Funder
Jilin Provincial Natural Science Foundation
Reference30 articles.
1. Insulation co-ordination of GIS: Return of experience, on site tests and diagnostic techniques;Sabot;Electra,1998
2. Dependence of Particle Initiated PD Characteristics on Size and Position of Metallic Particle Adhering to the Spacer Surface in GIS;Budiman;Waset Org.,2013
3. Partial Discharge and Breakdown Properties in Dry air, N2, CO2 under Non-uniform Electric Field;Inami;IEEE Trans. Dielectr. Electr. Insul.,2023
4. Partial discharge test under standard oscillating impulses on a gas-insulated bus with artificial metal particle defects on the insulator surface;Ren;IEEE Trans. Dielectr. Electr. Insul.,2016
5. Discharge Characteristics and Detectability of Metal Particles on the Spacer Surface in Gas-Insulated Switchgears;Li;IEEE Trans. Power Deliv.,2022
Cited by
5 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献