Abstract
An experimental investigation is conducted to measure and correlate the impact of the water content on the electrical characteristics of the mineral oil for transformers, particularly the breakdown voltage, the resistivity, and the dielectric dissipation factor. Regression method is carried out to compare the results obtained through laboratory experiments with those predicted using an analytical model. A treatment to reduce water content in oil involving filtration, degassing and dehydration using a SESCO mobile station was applied to the new, regenerated, and used oil samples in service. The breakdown voltage, the resistivity, and the dielectric dissipation factor of the samples were measured. Regression analysis using an exponential model was applied to examine the samples electrical properties. The results show that, after treatment, the breakdown voltage and resistivity increase as the water content decreases, unlike the dielectric dissipation factor which exhibits a decreasing trend. This trend is found to be similar for the three oil samples: new, regenerated, and used. The results of the regression analysis give close agreement with the experimental results for all the samples and all studied characteristics. The model shows strong correlation with high coefficients (>90%).
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous)
Cited by
15 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献