Author:
Lin Chang-Ming,Liu Hsin-Yu,Tseng Ko-Ying,Lin Sheng-Fuu
Abstract
The objective of this study was to develop a heating, ventilation, and air conditioning (HVAC) system optimization control strategy involving fan coil unit (FCU) temperature control for energy conservation in chilled water systems to enhance the operating efficiency of HVAC systems. The proposed control strategy involves three techniques, which are described as follows. The first technique is an algorithm for dynamic FCU temperature setting, which enables the FCU temperature to be set in accordance with changes in the outdoor temperature to satisfy the indoor thermal comfort for occupants. The second technique is an approach for determining the indoor cold air demand, which collects the set FCU temperature and converts it to the refrigeration ton required for the chilled water system; this serves as the control target for ensuring optimal HVAC operation. The third technique is a genetic algorithm for calculating the minimum energy consumption for an HVAC system. The genetic algorithm determines the pump operating frequency associated with minimum energy consumption per refrigeration ton to control energy conservation. To demonstrate the effectiveness of the proposed HVAC system optimization control strategy combining FCU temperature control, this study conducted a field experiment. The results revealed that the proposed strategy enabled an HVAC system to achieve 39.71% energy conservation compared with an HVAC system operating at full load.
Funder
Bureau of Energy, Ministry of Economic Affairs, Republic of Taiwan
Subject
Fluid Flow and Transfer Processes,Computer Science Applications,Process Chemistry and Technology,General Engineering,Instrumentation,General Materials Science
Cited by
16 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献