Abstract
Recently, as interest in eco-friendly distributed power has increased, studies on the improvement of the performance of breakers such as DC breakers and on the reliability of existing AC breakers have been actively conducted. To improve the performance and reliability of these breakers, this paper conducted the analysis of characteristics of a low voltage circuit breaker using an external magnetic field. In this experiment, before the current-zero point, the cut-off time to improve the breaker performance is shortened and after the current-zero point, re-ignition, which is associated with reliability, is suppressed. According to the experimental results, the short-circuit characteristics before current-zero show a significant difference of 0.13 ms in the t21 section, and the dielectric recovery strength after current-zero shows a 13.3% performance improvement in the latter half of the DRV (dielectric recovery voltage) V-t curve. This result has significant meaning because it can be easily improved under the control of the external magnetic field. Hence, it can be applied to the interruption performance improvement of breakers through detailed research in the future.
Funder
National Research Foundation of Kore
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous),Building and Construction
Cited by
1 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献