Abstract
Hospital surgical suites are high consumers of energy due to the strict indoor air quality (IAQ) conditions. However, by varying the ventilation strategies, the potential for energy savings is great, particularly during periods without activity. In addition, there is no international consensus on the ventilation and hygrothermal requirements for surgical areas. In this work, a dynamic energy model of a surgical suite of a Spanish hospital is developed. This energy model is calibrated and validated with experimental data collected during real operation. The model is used to simulate the yearly energy performance of the surgical suite under different ventilation scenarios. The common issue in the studied ventilation strategies is that the hygrothermal conditions ranges are extended during off-use hours. The maximum savings obtained are around 70% of the energy demand without compromising the safety and health of patients and medical staff, as the study complies with current heating, ventilation and air conditioning (HVAC) regulations.
Funder
European Regional Development Fund
Subject
Fluid Flow and Transfer Processes,Computer Science Applications,Process Chemistry and Technology,General Engineering,Instrumentation,General Materials Science
Cited by
11 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献