Affiliation:
1. Department of Electrical and Information Engineering, University of Cassino and Southern Lazio, Via G. Di Biasio 43, 03043 Cassino, Italy
Abstract
Active Distribution Networks are Multi-Input Multi-Output (MIMO) systems with coupled dynamics, which cause interactions among the control loops of Distributed Energy Resources (DERs). This undesired effect leads to performance degradation of voltage control. To mitigate the effects of this unavoidable coupling, the present paper proposes a systematic design procedure based on the analysis of the interaction’s sources. In detail, each DER is equipped with a double-loop PI to control the active and reactive power output of the voltage source converter, which connects the DER to the network’s node. Furthermore, to guarantee ancillary services, the two loops are coupled by a simple mechanism of cooperation of the active power to voltage regulation realized by a filtered droop law. To achieve voltage regulation with reduced loop interactions, the PI parameters and the filter’s pulse are designed according to a procedure with two sequential steps based on the Internal Model Control (IMC) technique. Simulation studies are finally presented to demonstrate that the proposed design method achieves both reduction of the loop interaction and robust voltage control in the presence of model parameter uncertainty in the MIMO plant, modeling various operating conditions of the ADN, including a step connection of large loads, renewable energy source variations, and changes in the substation transformer ratio.
Funder
Ecosistema dell’innovazione-Rome Technopole
Cited by
1 articles.
订阅此论文施引文献