Abstract
This study aims to provide an experimental investigation and comparison of the condensation heat transfer characteristics in a plate–fin heat exchanger (PFHE). The heat flux, mass flux, and saturation pressure were adjusted as experimental parameters to verify the effects on the condensation heat transfer. In addition, condensation heat transfer correlation of two-stream PFHEs was provided based on the experimental data for utilization as a design reference for the heat exchanger. The turbulence is the most influential in heat transfer. One of the ways to foster turbulence is to increase shear stress. The higher flow velocity results in the higher shear stress. That was why increasing mass flux or the flow with higher vapor quality showed the higher heat transfer coefficient (HTC). Refrigerant properties such as viscosity and specific volume of vapor changed according to the saturation pressure. It is expected they affect the degree of turbulence too in similar manners. The mass flux was more influential than the heat flux and saturation pressure. Thus, the equivalent mass flux of the refrigerant is dominant in the derived correlation model. The average difference between experimental and calculated HTC from correlations was about 6.5%. Multi-stream PFHE comprises an additional heat transfer surface, which implies a more active droplet formation. The average pressure drop in the multi-stream is 15% larger than that of the two-stream.
Funder
Ministry of Land, Infrastructure and Transport
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous)
Cited by
5 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献