Affiliation:
1. The Higher Educational Key Laboratory for Measuring & Control Technology and Instrumentation of Heilongjiang Province, Harbin University of Science and Technology, Harbin 150080, China
2. College of Engineering, Inner Mongolia Minzu University, Tongliao 028000, China
Abstract
With the increase of the penetration rate of renewable energy power generation in the power system, the power grid gradually tends to be weak. Under the scenario of nonlinear load connecting to weak power grid, the grid-side voltage will produce unbalance, distortion and frequency deviation due to the influence of large internal impedance, insufficient inertia, three-phase current unbalance and harmonics of weak power grid. The operation of active power filters (APF) under above conditions can lead to significant degradation in harmonic compensation performance. An adaptive proportional integral (PI) + vector PI (VPI) harmonic compensation strategy for a three-phase APF is proposed for use in complex conditions of weak grid. The strategy consists of an adaptive notch filter based synchronous phase-locked loop (ANF-PLL) and an adaptive PI + VPI current control method. In this strategy, a series of adaptive lattice notch filters are introduced to improve the accuracy of grid phase and frequency estimation under the condition of voltage unbalance, distortion and a large range of frequency deviation. Then the phase and frequency information are used in the Park transformation of harmonic detection and current compensation control and the update of PI + VPI current control law parameters. A VPI current tracking controller with adaptive resonant frequency is constructed, which can improve the gain of the resonant frequency point and ensure that the APF can maintain the best compensation performance under the above weak grid conditions. Finally, the simulation and experimental results indicate that the ANF-PLL shows a better phase and frequency estimation performance under complex conditions of weak grid than the conventional and notch filter based methods, and the harmonic compensation strategy presented in this paper achieves a significant performance improvement under complex conditions of weak grid compared with Fixed VPI/SRF-PLL strategy and adaptive VPI/NF-PLL strategy.
Funder
National Natural Science Foundation of China
Inner Mongolia Natural Science Foundation of China
Inner Mongolia Autonomous Region Talent Development Project Foundation of China
Subject
Fluid Flow and Transfer Processes,Computer Science Applications,Process Chemistry and Technology,General Engineering,Instrumentation,General Materials Science
Reference32 articles.
1. On the inertia of future more-electronics power systems;Fang;IEEE J. Emerg. Sel. Top. Power Electron.,2018
2. Impedance-phased dynamic control method for grid-connected inverters in a weak grid;Chen;IEEE Trans. Power Electron.,2016
3. Yoon, S.J., Tran, T.V., and Kim, K.H. (2020). Stability assessment of current controller with harmonic compensator for LCL-filtered grid-connected inverter under distorted weak grid. Appl. Sci., 11.
4. A Class of Nonlinear Active Disturbance Rejection Loop Filters for Phase-Locked Loop;Lin;IEEE Trans. Ind. Electron.,2021
5. A Novel Phase-Locked Loop with Improved-Dual Adaptive Notch Filter and Multi-Variable Filter;Pan;IEEE Access,2019
Cited by
4 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献