Design Selection Method of Exhaust Air Heat Recovery Type Indirect Evaporative Cooler

Author:

Guo Chunmei1,Li Yu1,Li Xianli1,Bai Ruxue1,Dong Chuanshuai2

Affiliation:

1. School of Energy and Safety Engineering, Tianjin Chengjian University, Tianjin 300384, China

2. Key Laboratory of Enhanced Heat Transfer and Energy Conservation of Education Ministry, School of Chemistry and Chemical Engineering, South China University of Technology, Guangzhou 510640, China

Abstract

In order to promote the engineering application of indirect evaporative cooling (IEC) in the field of building air conditioning, as well as reduce air conditioning energy consumption and carbon emissions, this paper proposes a fresh air unit using indirect evaporative cooling to achieve heat recovery from exhaust air, which gives the recommended values of air and spray water operation parameters. The indirect evaporative cooler heat and mass transfer mathematical model and numerical solution procedure were made. In summer outdoor design conditions, the fresh air outlet state parameters, cooling capacity, fresh air cooling load, wet bulb efficiency and enthalpy efficiency were numerically solved for thirty typical cities from five climate zones of China. In addition, also based on the model results for the cities in China, two representative operating conditions points of medium and high humidity were selected. Eight models of fresh air unit coolers in the air volume range of 1000–10,000 m3/h commonly used in engineering were simulated to obtain the optimal heat transfer area and size selection of ERIEC heat exchangers for fresh air units, and economic analysis was performed. The results show that the wet bulb efficiency ranges from 0.67–0.98, and increases as the outdoor design wet bulb temperature decreases; the enthalpy efficiency ranges from 0.76–1.29, and increases as the outdoor design wet bulb temperature increases; and the fresh air load that the exhaust air heat recovery type indirect evaporative cooler can bear ranges from 55–100%, which could largely decrease the cold load of the matched surface cooler. As demonstrated, the energy-saving effect is remarkable.

Funder

National Natural Science Foundation of China

Publisher

MDPI AG

Subject

Management, Monitoring, Policy and Law,Renewable Energy, Sustainability and the Environment,Geography, Planning and Development,Building and Construction

Reference30 articles.

1. On-site experimental testing of a novel dew point evaporative cooler;Bruno;Energy Build.,2011

2. Numerical investigation of wet-bulb effectiveness and water consumption in one-and two-stage indirect evaporative coolers;Moshari;Energy Convers. Manag.,2016

3. Wang, Y.G., and Pei, X.Y. (2015, January 11). Experimental study on the cooling performance of fork-flow type dew point indirect evaporative cooler. Proceedings of the 6th National Conference on Building Environment and Equipment Technology Exchange, Guangzhou, China.

4. Design and performance analysis of porous vertical tube type indirect evaporative cooler;Fan;Fluid Mach.,2019

5. Indirect evaporative cooling of air to a sub-wet bulb temperature;Hasan;Appl. Therm. Eng.,2010

Cited by 4 articles. 订阅此论文施引文献 订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3