Investigation of a Hybridized Cascade Trigeneration Cycle Combined with a District Heating and Air Conditioning System Using Vapour Absorption Refrigeration Cooling: Energy and Exergy Assessments

Author:

Agberegha Larry1,Aigba Peter1ORCID,Nwigbo Solomon2,Onoroh Francis3,Samuel Olusegun14ORCID,Bako Tanko5ORCID,Der Oguzhan6ORCID,Ercetin Ali7ORCID,Sener Ramazan6ORCID

Affiliation:

1. Department of Mechanical Engineering, Federal University of Petroleum Resources, P.M.B 1221, Effurun 330102, Delta State, Nigeria

2. Department of Mechanical Engineering, Nnamdi Azikiwe University, Awka 420218, Anambra State, Nigeria

3. Department of Mechanical Engineering, University of Lagos, Akoka 101017, Lagos State, Nigeria

4. Department of Mechanical Engineering, University of South Africa, Science Campus, Florida 1710, South Africa

5. Department of Agricultural and Bio-Resources Engineering, Taraba State University, Jalingo 660213, Yobe State, Nigeria

6. Department of Marine Vehicles Management Engineering, Maritime Faculty, Bandırma Onyedi Eylul University, Bandırma 10200, Türkiye

7. Department of Naval Architecture and Marine Engineering, Maritime Faculty, Bandırma Onyedi Eylul University, Bandırma 10200, Türkiye

Abstract

The insufficiency of energy supply and availability remains a significant global energy challenge. This work proposes a novel approach to addressing global energy challenges by testing the supercritical property and conversion of low-temperature thermal heat into useful energy. It introduces a combined-cascade steam-to-steam trigeneration cycle integrated with vapour absorption refrigeration (VAR) and district heating systems. Energetic and exergetic techniques were applied to assess irreversibility and exergetic destruction. At a gas turbine power of 26.1 MW, energy and exergy efficiencies of 76.68% and 37.71% were achieved, respectively, while producing 17.98 MW of electricity from the steam-to-steam driven cascaded topping and bottoming plants. The cascaded plant attained an energetic efficiency of 38.45% and an exergy efficiency of 56.19%. The overall cycle efficiencies were 85.05% (energy) and 77.99% (exergy). More than 50% of the plant’s lost energy came from the combustion chamber of the gas turbine. The trigeneration system incorporated a binary NH3–H2O VAR system, emphasizing its significance in low-temperature energy systems. The VAR system achieved a cycle exergetic efficiency of 92.25% at a cooling capacity of 2.07 MW, utilizing recovered waste heat at 88 °C for district hot water. The recovered heat minimizes overall exergy destruction, enhancing thermal plant performance.

Publisher

MDPI AG

Reference119 articles.

1. IEA (2022). Gas Market Report, Q1-2022, International Energy Agency.

2. Dale, S. (2022). BP Statistical Review of World Energy, BP Publications. [71st ed.].

3. IEA (2021). COP26 Climate Pledges Could Help Limit Global Warming to 1.8 °C, but Implementing Them Will Be the Key, IEA.

4. Holz, F., Richter, P.M., and Egging, R. (2013). The Role of Natural Gas in a Low-Carbon Europe: Infrastructure and Regional Supply Security in the Global Gas Model, DIW Berlin—German Institute for Economic Research.

5. Exergoeconomic and exergoenvironmental analyses of a combined cycle power plant with chemical looping technology;Petrakopoulou;Int. J. Greenh. Gas Control,2011

Cited by 4 articles. 订阅此论文施引文献 订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献