Affiliation:
1. Electric Power Research Institute of State Grid Sichuan Electric Power Company, Chengdu 610041, China
2. Power Internet of Things Key Laboratory of Sichuan Province, Chengdu 610041, China
3. School of Mechanical and Electrical Engineering, University of Electronic Science and Technology of China, Chengdu 610059, China
Abstract
Dry-type air-core shunt reactors are integral components in power transmission and distribution networks, designed to control reactive power and enhance system stability. However, inter-turn short-circuit faults (ISCFs) are common occurrences in shunt reactors, which are caused by various factors, including manufacturing defects, insulation degradation, or operational stresses. At the early stage of the ISCFs, the current does not reach a sufficient level to activate the protective equipment. These faults may lead to serious consequences, such as overheating, insulation breakdown, and even catastrophic failures, posing risks to the entire power system. Therefore, developing an effective and reliable detection method for ISCFs at the early stage is paramount. In this paper, a new method named the fault detection factor (FDF) based on equivalent resistance is presented to detect the slight ISCFs in dry-type air-core shunt reactors considering insulation resistance. In addition, the effect of noise signal existence in the monitoring process is taken into account. A moving average filter is adopted to guarantee both the sensitivity and the reliability of the proposed method. Ultimately, the simulation results of the FDF under different conditions are presented, which show the effectiveness and potential of the proposed method in observing and monitoring slight ISCFs.
Funder
State Grid Sichuan Electric Power Company scientific project
Reference30 articles.
1. Research on five-loop simplified scaling model for dry-type air-core reactors with inter-turn short circuit fault;Sun;IEEE Access,2021
2. Breaking overvoltage of dry-type air-core shunt reactors and its cumulative effect on the interturn insulation;Nie;IEEE Access,2019
3. A novel hybrid differential algorithm for turn to turn fault detection in shunt reactors;Das;IEEE Trans. Power Deliv.,2017
4. A new differential protection algorithm for power reactors based on the second central moment;Andrade;Electr. Power Energy Syst.,2020
5. Operation analysis and operation and maintenance method of 35 kV dry-type air-core shunt reactor;Li;Electr. Eng.,2018
Cited by
1 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献