Abstract
Islanding detection methods, based on injecting high-/low-frequency currents or negative sequence fundamental frequency currents and observing the resultant responses, are collectively referred to as irregular current injection methods in this paper. In multi-distributed generation (DG) operation, if there is no restriction to the phase of injected irregular currents, the currents at the same frequency may cancel each other out, and then their convergent current may be too small to cause a detectable response, for which reason islanding detection will be severely affected. Accordingly, this paper raises a compatibility issue, which requires the phase difference between any two injected irregular currents to be within a certain interval. In response to this issue, a solution is proposed. According to this solution, the terminal voltage of DG units is referenced to conduct irregular currents injection, and only certain high-frequency currents are used as injected currents. If this solution is adopted by as many manufacturers as possible, the effect and reliability of such methods will be greatly improved.
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous)
Cited by
8 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献