Sensor Fault-Tolerant Control of Microgrid Using Robust Sliding-Mode Observer

Author:

Shahzad EbrahimORCID,Khan Adnan Umar,Iqbal Muhammad,Saeed AhmadORCID,Hafeez GhulamORCID,Waseem Athar,Albogamy Fahad R.,Ullah ZahidORCID

Abstract

This work investigates sensor fault diagnostics and fault-tolerant control for a voltage source converter based microgrid (model) using a sliding-mode observer. It aims to provide a diagnosis of multiple faults (i.e., magnitude, phase, and harmonics) occurring simultaneously or individually in current/potential transformers. A modified algorithm based on convex optimization is used to determine the gains of the sliding-mode observer, which utilizes the feasibility optimization or trace minimization of a Ricatti equation-based modification of H-Infinity (H∞) constrained linear matrix inequalities. The fault and disturbance estimation method is modified and improved with some corrections in previous works. The stability and finite-time reachability of the observers are also presented for the considered faulty and perturbed microgrid system. A proportional-integral (PI) based control is utilized for the conventional regulations required for frequency and voltage sags occurring in a microgrid. However, the same control block features fault-tolerant control (FTC) functionality. It is attained by incorporating a sliding-mode observer to reconstruct the faults of sensors (transformers), which are fed to the control block after correction. Simulation-based analysis is performed by presenting the results of state/output estimation, state/output estimation errors, fault reconstruction, estimated disturbances, and fault-tolerant control performance. Simulations are performed for sinusoidal, constant, linearly increasing, intermittent, sawtooth, and random sort of often occurring sensor faults. However, this paper includes results for the sinusoidal nature voltage/current sensor (transformer) fault and a linearly increasing type of fault, whereas the remaining results are part of the supplementary data file. The comparison analysis is performed in terms of observer gains being estimated by previously used techniques as compared to the proposed modified approach. It also includes the comparison of the voltage-frequency control implemented with and without the incorporation of the used observer based fault estimation and corrections, in the control block. The faults here are considered for voltage/current sensor transformers, but the approach works for a wide range of sensors.

Publisher

MDPI AG

Subject

Electrical and Electronic Engineering,Biochemistry,Instrumentation,Atomic and Molecular Physics, and Optics,Analytical Chemistry

Reference51 articles.

1. Trends in microgrid control;Olivares;IEEE Trans. Smart Grid,2014

2. Control of power converters in AC microgrids;Rocabert;IEEE Trans. Power Electron.,2012

3. Hierarchical control of intelligent microgrids;Vasquez;IEEE Ind. Electron. Mag.,2010

4. Fault tolerant control of power grids;Odgaard;Int. J. Robust Nonlinear Control,2014

Cited by 6 articles. 订阅此论文施引文献 订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献