Abstract
Traditional high-voltage reactor monitoring and diagnosis research has problems such as high sampling demand, difficulty in noise reduction on site, many false alarms, and lack of on-site data. In order to solve the above problems, this paper proposes an acoustic–electric fusion high-voltage reactor acquisition system and defect diagnosis method based on reactor pulse current and ultrasonic detection signal. Using the envelope peak signal as the basic detection data, the sampling requirement of the system is reduced. To fill the missing data with partial discharge (PD) information, a method based on k-nearest neighbor (KNN) is proposed. An adaptive noise reduction method is carried out, and a noise threshold calculation method is given for the field sensors. A joint analysis method of acoustic and electrical signals based on correlation significance is established to determine whether a discharge event has occurred based on correlation significance. Finally, the method is applied to a UHV reactor on the spot, which proves the effectiveness of the method proposed in this paper.
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous),Building and Construction