Impact of First Tower Earthing Resistance on Fast Front Back-Flashover in a 66 kV Transmission System

Author:

Moselhy Abdullah H.ORCID,Abdel-Aziz Abdelaziz M.,Gilany Mahmoud,Emam AhmedORCID

Abstract

Lightning stroke on a transmission tower structure is one of the major reasons that results in high voltages at the tower arms due to the excessive lightning current flowing through the transmission tower to earth. The Surge voltage seen at the tower cross arm on the first tower close to a substation is the worst case. If this voltage is higher than the withstand level of the insulator string, the insulation of substation equipment will be exposed to transient over-voltage called fast front back-flashover (FFBF). The peak of this transient overvoltage is affected by the value of the system’s earthing resistance. This paper studies the effect of reducing the grounding resistance of both the surge arrestor (SA) and the first transmission line tower adjacent to a 66 kV substation on FFBF. Three case studies using PSCAD/EMTDC software are presented to simulate the variation of the potential sire at the substation equipment with different resistance values for the first tower and SA earthing resistance. The paper also addresses the economic protection system for solving the problem of transient overvoltage. The study proves that the proper design of the first tower grounding system enhances the safety of the system and reduces the cost for the grounding system to the minimum.

Publisher

MDPI AG

Subject

Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous)

Reference54 articles.

1. Lightning Studies, Webinar on Lightning Over Voltage Simulations in PSCADTM EMTDCTM 2016;Muthumuni,2016

2. Insulation coordination study for a 50 kV traction feeder station

3. IEC 60071-2 International Standard Internationale, Insulation co-ordination–Part. 2,2008

4. Study of Tower Grounding Resistance Effected Back Flashover to 500 kV Transmission Line in Thailand by using ATP/EMTP;Marungsri;Int. J. Energy Power Eng.,2009

Cited by 3 articles. 订阅此论文施引文献 订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3