Study on Effects of Operating Parameters on a Water-Cooled Loop Thermosyphon System under Partial Server Utilization

Author:

Zou Sikai1,Yue Chang2,Xiao Ting1,Ma Xingyi1,Wang Yiwei1

Affiliation:

1. School of Civil Engineering and Architecture, East China JiaoTong University, Nanchang 330013, China

2. School of Energy Science and Engineering, Central South University, Changsha 410083, China

Abstract

During the operation of a data center, servers are gradually installed in racks, causing most racks to work under a low heating load for a long time and affecting the cooling efficiency of the loop thermosyphon system (LTS). Thus, the effects of operating parameters on the thermal performance should be investigated. In this study, a water-cooled LTS was experimentally investigated under different airflow rates and heating loads. The results show that the additional liquid refrigerant reduced the heat transfer performance and aggravated a drop in cooling capacity when the airflow rate and heating load were decreased. To further reveal the effects of the operating parameters on the thermal performance and cooling efficiency, a steady-state distributed-parameter model was developed and validated based on the experimental data. The results show that the excessive cooling capacity was reduced by decreasing the airflow rate according to the upper limit of the server exhaust air temperature under partial server utilization. The excessive cooling capacity was reduced by 14.5–52.1% under 5–56.5% server utilization. To further reduce the excessive cooling capacity while ensuring thermal security, the water side operating parameters (including the supply chilled water temperature and water flow rate) were adjusted according to the upper limit of the rack’s average outlet air temperature, which reduced the excessive cooling capacity by more than 23.8% under partial server utilization.

Funder

National Natural Science Found of China

Jiangxi Provincial Natural Science Foundation

the Science and Technology Research Project of Education Department of Jiangxi Province

Publisher

MDPI AG

Subject

Management, Monitoring, Policy and Law,Renewable Energy, Sustainability and the Environment,Geography, Planning and Development,Building and Construction

Reference48 articles.

1. Zhang, W., Zhang, S., Wang, X., Qiao, J., Zhang, J., and Kong, W. (2019). Lighting up the Green Cloud: A Study on Energy Consumption and Renewable Energy Usage Potential of Data Centers in China, North China Electric Power University.

2. A review of thermal management and innovative cooling strategies for data center;Nadjahi;Sustain. Comput. Inform. Syst.,2018

3. Simplified server model to simulate data center cooling energy consumption;Ham;Energy Build.,2015

4. Cooling technologies for data centres and telecommunication base stations—A comprehensive review;Zhang;J. Clean. Prod.,2022

5. Study of ventilation cooling technology for telecommunication base stations in Guangzhou;Chen;Energy Build.,2009

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3