Abstract
This paper presents the mathematical model and control of the voltage source inverter (VSI) connected to an alternating current (AC) microgrid. The VSI used in this work was a six-switch three-phase PWM inverter, whose output voltages were controlled in a synchronous (dq) reference frame via a sliding mode control strategy. The control strategy required only output voltages; other states of the system were estimated by using a high-gain observer. The power-sharing among multiple inverters was achieved by solving power flow equations of the electrical network. The stability analysis showed that the error was ultimately bound in the case of the real PWM inverter and/or with a nonlinear load in the electrical network. The microgrid was simulated using the SimPowerSystems Toolbox from MATLAB/Simulink. The simulation results show the effectiveness of the proposed control scheme. The output voltage regulation of the inverter and power-sharing was achieved with the ultimately bounded error for the linear load. Later, the nonlinear load was also included in the electrical network and the error was shown to remain ultimately bounded. The output voltage regulation and power-sharing were achieved with the nonlinear load in the system.
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous),Building and Construction
Cited by
2 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献