Abstract
Cross-linked polyethylene (XLPE) carries a high fire risk. In this paper, a cone calorimeter is used to carry out radiation ignition experiments, and the heat release rate (HRR), mass loss rate (MLR) and other combustion parameters of XLPE cables under three kinds of radiation intensity are measured. By comparing the ignition time and HRR of samples under different conditions, the following conclusions are drawn: (1) The ignition time of XLPE cables decreases significantly with the increase in external thermal radiation intensity. The critical ignition heat flux (CHF) is about 16.24 kW/m2. (2) The HRR curve of XLPE is consistent with the characteristics of hot, thick material. The HRR rises rapidly to the first peak after ignition and then rapidly decreases. Then, it slowly rises to the second peak. Finally, it slowly decays until the combustion stops. (3) The first peak values of HRR of XLPE under different radiation intensities are almost the same. The time for the second peak of HRR is shorter, and the value is larger with the increase in external thermal radiation intensity. (4) The cable ignition model is established, which can simulate the cable ignition time well under different radiant heat flow conditions. (5) Based on the mathematical model, the ignition time trend with the thickness of sheath layer and conductive core layer as variables is deduced.
Funder
State Grid Shandong electric power company science and technology project
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous),Building and Construction
Cited by
10 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献