Lightning Protection of the Explosion Airflow Arc-Quenching Gap for 110 kV Transmission Lines
Author:
Wu Dong,Wang Ju-feng
Abstract
With the increase in the voltage level and number of transmission lines, the probability of lightning strikes on transmission lines is significantly increased, while lightning breakage accidents occur frequently. Therefore, an explosion airflow arc-quenching gap for 110 kV transmission lines was developed based on the idea of rapid extinction. A mathematical model of the detonation wave based on the CJ (Chapman–Jouget) detonation wave theory was developed to calculate the detonation air pressure and analyze its influencing factors. ANSYS software and the magnetohydrodynamic (MHD) model were used to simulate the process of detonation airflow coupled with an arc, and the simulation results indicated that the power frequency arc was evidently suppressed with the influence of airflow, which can effectively prevent arcing. A combined impulse and power frequency test and arc-quenching tests were performed to verify the effectiveness of the arc-quenching gap. The results of the combined test indicated that the arc burn time was 0.1 ms and that no power frequency continuous current was displayed. The results ensured the accuracy of the simulation model. The results of the arc-quenching tests proved that the explosion airflow can extinguish a power frequency arc with an amplitude of 40 kA in half of a power frequency arc cycle.
Funder
National Natural Science Foundation of China
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous)
Reference22 articles.
1. Review on Lightning Performance Estimation of EHV and UHV Overhead Transmission Lines in China Southern Power Grid;He;South. Power Syst. Technol.,2016
2. Present Status and Development Trend of Lightning Detection and Protection Technology of Power Grid in China;Chen;High Volt. Eng.,2016
3. Finite difference time domain simulation of lightning transient electromagnetic fields on transmission lines;Yao;IEEE Trans. Dielectr. Electr. Insul.,2013
4. Lightning Protection Study of Transmission Line, Part Ⅲ: Protection Measures;He;High Volt. Technol.,2009
5. Analysis of aspects of lightning strokes to large-sized transmission lines
Cited by
1 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献