Abstract
Few experiments have been performed to investigate the hydraulic performance in a chevron brazed plate heat exchanger (BPHE) with the narrow channel at lower Reynolds number. The hydraulic characteristics of seven types of chevron BPHEs were investigated experimentally and numerical simulation revealed the effects of structural parameters on hydraulic performances. The correlations between friction factor f and Re were fitted out based on more than 500 sets of pressure drop data. The research results show that there is a power-law between f and Re; which has a similar trend but a different amplitude for different plates, and the exponent of the power-law could be approximate to a constant. Numerical results show that the pressure drop Δp is positively correlated with the corrugated angle and spacing, however, negatively correlated with the corrugated height. Research on the hydraulic performance is significant for the optimal design of BPHE.
Funder
Natural Science Foundation of Zhejiang Province
National Natural Science Foundation of China
Subject
Process Chemistry and Technology,Chemical Engineering (miscellaneous),Bioengineering
Cited by
13 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献