Analysis on the Effect of Obstruction on Sprinkler Skipping in Air Conditioner Room Fire
Author:
Kim Ji TaeORCID,
Nam Jun Suk,
Kim Ryang Hoon,
Kim Seung Yeon,
Ryou Hong SunORCID
Abstract
Sprinkler skipping is an important issue in fire spread. In general, two sprinklers are installed in air conditioner rooms at the ceiling and 30 cm below to avoid spray failure by energy recovery ventilator in the ceiling. However, there is a problem in that sprinkler skipping occurs in the air conditioner room. In this study, the sprinkler skipping phenomenon was analyzed through numerical analysis and the applicability of the open type of sprinkler operation method was reviewed. As a result, when the upper sprinkler works, sprinkler skipping occurred in all cases. The lower sprinkler shall not rise above the operating temperature of 68.3 °C with a maximum temperature of 65 °C. In particular, the spray failure caused by the energy recovery ventilator reduces the sprinkler head temperature by more than 8 °C by concentrating the spray droplets. As an open type, simultaneous operation of two sprinklers is capable of obtaining an appropriate fire extinguishing effect by covering the fire source with the spray of the lower sprinkler. The research results are expected to help in fire protection in buildings such as modern apartments with air-conditioned rooms.
Funder
Ministry of SMEs and Startup
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous),Building and Construction
Reference15 articles.
1. An Investigation of the Causative Mechanism of Sprinkler Skipping
2. The Scaling of Sprinkler Discharge: Prediction of Drop Size;Dundas,1974
3. Similarity Relations for the Initial Convective Flow Generated by Fire;Heskestad,1972
4. Air Entrainment into Water Sprays;Heskestad,1981
5. Cooling and Penetration Study;Dundas,1974