Author:
Li Xiong,Li Chengrong,Bai Feng,Cao Fangyuan
Abstract
It is very important to calculate the interference of high voltage direct current (HVDC) grounding current with pipelines accurately and take proper protective measures to ensure energy transmission safety. There is still a lack of systematic research into related prediction methods that consider the nonlinear polarization on the interface between the soil and pipelines. In this paper, a methodology is proposed for calculating the coupling voltage and current on buried pipelines induced by grounding currents that accounts for nonlinear polarization based on the method of moments (MoM) and the finite element method (FEM). The validity of the proposed mathematical model is verified by a scale experiment. The interference distribution characteristics under different parameters are analyzed using the proposed method. The results show that the relationship between the maximum leakage current density and the electrode grounding current satisfy the linear function. The corrosion area becomes more concentrated as the grounding current increases. The corrosion area range increases substantially as the distance increases, whereas the influence degree decreases substantially. Both the maximum leakage current density and corrosion risk area are positively correlated with the soil resistivity.
Subject
Fluid Flow and Transfer Processes,Computer Science Applications,Process Chemistry and Technology,General Engineering,Instrumentation,General Materials Science
Cited by
5 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献