Abstract
High frequency resonance (HFR) is a subsistent problem which affects the operation of the voltage source converter (VSC) connected to the parallel compensated grid. The appearance of HFR introduces a significant high frequency component in the grid voltage, thereby the operation of VSC system will be seriously affected. For enhancing the operation capability of VSC system, an HFR damping method based on the voltage feedforward control is proposed in this paper, which can reshape the VSC system impedance effectively in a wideband range. Besides, different with the existing HFR damping methods, the proposed method introduces a correction factor instead of the series virtual impedance with fixed value, so that the effect of impedance reshaping is irrelevant to the parameters of controlled object. In addition, this paper analyzes the fundamental control performance of VSC system after equipping the proposed method, for verifying that the proposed method will not worsen the fundamental control. Experimental results are given to validate the effectiveness of the proposed damping method.
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous)
Cited by
2 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献