Time Estimation Algorithm of Single-Phase-to-Ground Fault Based on Two-Step Dimensionality Reduction

Author:

Lin Xin1,Chen Haoran1ORCID,Xu Kai2,Xu Jianyuan1

Affiliation:

1. College of Electrical Engineering, Shenyang University of Technology, Shenyang 110870, China

2. State Grid Liaoning Electric Power Co., Ltd., Shenyang 110006, China

Abstract

The fault detection time identified by relying on the over-voltage criterion of zero-sequence voltage often lags behind the actual occurrence time of ground faults, which may cause fault protection methods based on transient quantity principles to miss fault characteristics and lose their protection capability. To accurately estimate the time of occurrence of a single-phase-to-ground fault, this paper proposes a two-step dimensionality reduction algorithm for estimating the time of occurrence of a single-phase-to-ground fault in a distribution network. This algorithm constructs a filter based on Empirical Mode Decomposition (EMD) to establish a high-dimensional feature dataset based on the zero-sequence current of all feeders. After Principal Component Analysis and Hilbert Mapping Algorithm, the high-dimensional data are reduced to two dimensions to construct a two-dimensional feature dataset. The density-based clustering method is used to adaptively divide the data into two categories, fault data and non-fault data, so as to estimate the time of occurrence of the fault. The paper designs 11 sets of experiments including 7 common high-resistance grounding mediums to verify the accuracy of the fault time recognition of this algorithm. The accuracy of this algorithm is within 7.3 ms and it exhibits better detection performance compared to the threshold detection method.

Publisher

MDPI AG

Subject

Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous),Building and Construction

Reference26 articles.

1. Practical high-impedance fault detection on distribution feeders;Benner;IEEE Trans. Ind. Appl.,1997

2. Modeling and simulation analysis of arc in distribution network;Xu;Power Syst. Prot. Control,2015

3. Analysis of the arc high impedance grounding faults voltage characteristics in non-effective grounding feeders;Qiu;Power Syst. Prot. Control,2019

4. High impedance fault location in 11 kV underground distribution systems using wavelet transforms;Bakar;Int. J. Electr. Power Energy Syst.,2014

5. High impedance fault detection: A review;Ghaderi;Electr. Power Syst. Res.,2017