Response Characteristics of Smoke Detection for Reduction of Unwanted Fire Alarms in Studio-Type Apartments

Author:

Hwang Euy-hong1ORCID,Choi Han-bit1ORCID,Choi Don-mook1

Affiliation:

1. Department of Equipment System and Fire Protection Engineering, Gachon University, 1342, Seongnam-daero, Sujeong-gu, Seongnam-si 13120, Republic of Korea

Abstract

Photoelectric smoke detectors (SDs) often emit false alarms in studio-type apartments, where fire prevention is crucial. This study investigates the response characteristics of conventional and analog smoke detection factors to reduce false positives in studio-type apartments. A mock-up was tested based on relevant domestic laws, standards, statistical data, and experimental cases. A simulation of a cooking scenario involving burned food items was conducted, and optical density, particulate matter (PM), and carbon monoxide levels were measured and compared with actual smoke detection at six different locations. The measured values of conventional smoke detectors (CSDs) and analog smoke detectors (ASDs) at these locations were used to derive the activation time of CSDs and ASDs for the entire mock-up space. The results showed that the CSD activated at 7.42 min, while the ASD activated at 11.57 min. PM10.0, CO, and CO2 showed similar activation time trends. The PM10.0, CO, and CO2 concentrations at the time of SD activation were estimated. The findings suggest that a sensor with a consistent coefficient of variation, such as PM10.0 and CO, should be recommended.

Publisher

MDPI AG

Subject

Earth and Planetary Sciences (miscellaneous),Safety Research,Environmental Science (miscellaneous),Safety, Risk, Reliability and Quality,Building and Construction,Forestry

Reference18 articles.

1. Till, R.C., and Coon, J.W. (2019). Fire Protection; Detection, Notification, and Suppression, Springer International Publishing. [2nd ed.].

2. NFSC 203 (2015). Automatic Fire Detection System and Visual Warning Device Fire Safety Codes, Ministry of Public Administration and Security.

3. Estimation of fire detection time;Qiang;Procedia Eng.,2011

4. Experimental analysis on false alarms of fire detectors by cooking fumes;Qiyuan;J. Fire Sci.,2004

5. Design of Detection System;Hurley;SFPE Handbook of Fire Protection Engineering,2016

Cited by 1 articles. 订阅此论文施引文献 订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3