Abstract
Radon poses significant health risks. Thus, the continuous monitoring of radon concentrations in buildings’ indoor air is relevant, particularly in schools. Low-cost sensors devices are emerging as promising technologies, although their reliability is still unknown. Therefore, this is the first study aiming to evaluate the performance of low-cost sensors devices for short-term continuous radon monitoring in the indoor air of nursery and primary school buildings. Five classrooms of different age groups (infants, pre-schoolers and primary school children) were selected from one nursery and one primary school in Porto (Portugal). Radon indoor concentrations were continuously monitored using one reference instrument (Radim 5B) and three commercially available low-cost sensors devices (Airthings Wave and RandonEye: RD200 and RD200P2) for short-term sampling (2–4 consecutive days) in each studied classroom. Radon concentrations were in accordance with the typical profiles found in other studies (higher on weekends and non-occupancy periods than on occupancy). Both RadonEye low-cost sensors devices presented similar profiles with Radim 5B and good performance indices (R2 reaching 0.961), while the Airthings Wave behavior was quite different. These results seem to indicate that the RadonEye low-cost sensors devices studied can be used in short-term radon monitoring, being promising tools for actively reducing indoor radon concentrations.
Funder
Fundação para a Ciência e Tecnologia
Subject
Management, Monitoring, Policy and Law,Renewable Energy, Sustainability and the Environment,Geography, Planning and Development
Cited by
19 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献