Abstract
In view of the fact that the partial discharge (PD) signal energy is mainly concentrated below hundreds of megahertz, the ultra-high frequency part of the energy is weak, and the interior space of the switchgear is narrow, this paper proposes a new method for PD detection of the switchgear based on near-field detection. Firstly, based on the principle of PD, the field characteristics of the signal in the switchgear are analyzed. After that, the probe is designed with an electric small loop structure. Based on its equivalent circuit, its measurement principle and amplitude frequency characteristics are analyzed. The influence of probe size and material on amplitude frequency characteristics is obtained by using simulation software High Frequency Structure Simulator (HFSS), and the probe parameters suitable for PD detection in the switchgear are determined. Finally, the performance of the probe is measured by network analyzer, and the PD signal is tested on the simulated PD test platform. The results show that the probe works in the frequency band of 10–200 MHz and can receive PD signals containing more energy information. In the operating frequency band, the reflection coefficient of the probe port is very large, and its interference to the signal near field is particularly small. The probe also has good frequency response characteristics, and the fluctuation in the frequency band is less than 5 dB, which can obtain more accurate PD signal characteristics in subsequent processing. In addition, the probe is passive, with dimensions of 166 mm in length, 104 mm in width, and 2 mm in thickness, which is suitable for placing in the switchgear with small internal space. The results of PD receiving test show that the probe can reflect the occurrence of PD remarkably and accurately.
Funder
Research and development of new smart sensor technology to promote the development of green energy
Research and development of key technologies for conformal implantation of new intelligent power sensing for power grid main equipment
Subject
Electrical and Electronic Engineering,Computer Networks and Communications,Hardware and Architecture,Signal Processing,Control and Systems Engineering
Reference34 articles.
1. Switchgear fault feature selection and diagnosis method based on improved Laplace score;Zhou;Power Syst. Technol.,2015
2. Detection and analysis of partial discharge characteristics of electrical equipment inside high-voltage switchgear;Li;High Volt. Appar.,2018
3. Online monitoring device for partial discharge in high-voltage switchgear based on pulse current method;Tao;Power Syst. Prot. Control.,2019
4. Zhang, X., Cheng, Z., and Gui, Y. (2016). Design of a New Built-in UHF Multi-Frequency Antenna Sensor for Partial Discharge Detection in High-Voltage Switchgears. Sensors, 16.
5. Pulse quantification in broadband pulse current method for partial discharge detection;Ruan;High Volt. Appar.,2009