Research on Non-Invasive Floating Ground Voltage Measurement and Calibration Method

Author:

Suo Chunguang1,He Mingxing1,Zhou Guoqiong1,Shi Xinghua1,Tan Xiangyu2,Zhang Wenbin3

Affiliation:

1. Faculty of Science, Kunming University of Science and Technology, Kunming 650504, China

2. Electric Power Research Institute, Yunnan Power Grid Co., Ltd., Kunming 650504, China

3. College of Mechanical and Electrical Engineering, Kunming University of Science and Technology, Kunming 650504, China

Abstract

Voltage measurement is an important part of power system operation, and non-intrusive voltage sensors have the advantages of low insulation difficulty, simple structure, easy loading and unloading, and high construction safety, which have become a new direction for voltage measurement. Based on the principle of electric field coupling, this paper constructs a non-intrusive floating ground three-capacitance voltage measurement model, which can complete the accurate measurement of voltage without connecting with the line to be measured and the earth in the measurement process. In non-intrusive voltage measurement, the change of the object to be measured or the measurement environment will cause the change of the coupling capacitance, which leads to the uncertainty of the transmission relationship of the sensor and the large error of measurement results. In order to solve this problem, a new method of sensor calibration is proposed in this paper. By sampling capacitance in parallel between two electrodes of the sensor, changing the capacitance value, and establishing an input output equation, the coupling capacitance value and the voltage value to be measured under different operating conditions are solved. In addition, the sampling capacitance is often several orders of magnitude larger than the sensor’s own capacitance, making the sensor’s voltage division ratio significantly higher and more conducive to the measurement of high voltages. The experimental results show that the measurement error is less than 2%, which verifies the feasibility of the method and the accuracy of the voltage measurement.

Funder

Yunnan Academy of Science and Technology “Research and development of new smart sensor technology to promote green energy development”

Scientific Research Foundation of Yunnan Provincial Department of Education

Publisher

MDPI AG

Subject

Electrical and Electronic Engineering,Computer Networks and Communications,Hardware and Architecture,Signal Processing,Control and Systems Engineering

Cited by 3 articles. 订阅此论文施引文献 订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3