Author:
Himanshu ,Singh Harsimran,Kumar Pandiyan,Ali Muhammad,Lee Ho,Khan Muhammad,Park Gwan,Kim Hee-Je
Abstract
The high-frequency-based medium voltage (MV) inverter is used in renewable energy power sources for power transmission. However, power quality is compromised as a result of the increase in common mode noise currents by the high inter-winding parasitic capacitance in high-frequency link transformers. This fast voltage transient response leads to harmonic distortion and transformer overheating, which causes power supply failure or many other electrical hazards. This paper presents a comparative study between conventional and modified toroid transformer designs for isolated power supply. A half bridge high-frequency (10 kHz) MV DC–AC inverter was designed along with power source; a 680 W solar module renewable system was built. An FEM-simulation with Matlab-FFT analysis was used to determine the core flux distribution and to calculate the total harmonics distortion (THD). A GWInstek LCR meter and Fluke VT04A measured the inter-winding capacitance and temperature in all four transformer prototypes, respectively. The modified design of a toroid ferrite core transformer offers more resistance to temperature increase without the use of any cooling agent or external circuitry, while reducing the parasitic capacitance by 87%. Experiments were conducted along with a mathematical derivation of the inter-winding capacitance to confirm the validity of the approach.
Subject
Electrical and Electronic Engineering,Computer Networks and Communications,Hardware and Architecture,Signal Processing,Control and Systems Engineering
Cited by
12 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献