Author:
Dai Jianfeng,Tang Yi,Yi Jun
Abstract
High-penetration wind power will count towards a significant portion of future power grid. This significant role requires wind turbine generators (WTGs) to contribute to voltage and reactive power support. The maximum reactive power capacity (MRPC) of a WTG depends on its current input wind speed, so that the reactive power regulating ability of the WTG itself and adjacent WTGs are not necessarily identical due to the variable wind speed and the wake effect. This paper proposes an adaptive gains control scheme (AGCS) for a permanent magnet synchronous generator (PMSG)-based wind power plant (WPP) to provide a voltage regulation service that can enhance the voltage-support capability under load disturbance and various wind conditions. The droop gains of the voltage controller for PMSGs are spatially and temporally dependent variables and adjusted adaptively depending on the MRPC which are a function of the current variable wind speed. Thus, WTGs with lower input wind speed can provide greater reactive power capability. The proposed AGCS is demonstrated by using a PSCAD/EMTDC simulator. It can be concluded that, compared with the conventional fixed-gains control scheme (FGCS), the proposed method can effectively improve the voltage-support capacity while ensuring stable operation of all PMSGs in WPP, especially under high wind speed conditions.
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous)
Cited by
7 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献