Abstract
As a part of the initial investigation of fire damage diagnosis, fire protection-applied specimens within petrochemical plant facilities were exposed to standard and hydrocarbon fire conditions; then, the heating temperature of the specimens was monitored, and their appearance was checked by visual observation. Although data on the appearance status for discoloration, thickness variations, etc. of fire protection were collated for each set of fire exposure conditions, it was difficult to estimate the heating temperature of the specimens. Therefore, the visual observation method for determining the degree of fire damage needs to be approached somewhat conservatively. Moreover, according to the results of the heating temperature measurements for each specimen, it was confirmed that the paint has a disadvantage in maintaining its fire resistance performance when exposed to a hydrocarbon fire.
Funder
Ministry of Land, Infrastructure and Transport
Korea Agency for Infrastructure Technology Advancement
Publisher
Korean Society of Hazard Mitigation
Cited by
3 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献