Structural Optimization Design of Three Phase Enclosed GIS Disconnector Based on MOGOA and ELM

Author:

Ding Can1,Wang Zhoulin1,Li Jinqi1,Ding Yiling1

Affiliation:

1. College of Electrical Engineering & New Energy, China Three Gorges University Yichang Hubei China

Abstract

Due to the compact and complex internal structure of 110 kV three‐phase enclosed GIS disconnector, the voltage distribution between the contact breaks of each phase has an influence on the insulation performance of the GIS disconnector, and its internal insulation design is a difficult point to be solved. To solve this problem, this paper firstly establishes a three‐dimensional model of three‐phase enclosed GIS disconnecting switch and conducts a research on the distribution of electric field under a specific working condition, it is found that the outer corner of the static contact, the inner corner of the static arc contact, the inner corner of the outer end of the moving contact and the inner corner of the moving contact are the internal electric field concentration of the three‐phase enclosed GIS disconnector. Then, in order to further reduce the electric field strength and improve the insulation margin and performance, this paper proposes a method based on the combination of Extreme Learning Machine (ELM) and Multi‐objective Grasshopper Optimization Algorithm (MOGOA) to optimize the structural design of three‐phase enclosed GIS disconnector, and a ELM model is established, which takes the internal fillet radius of stationary arcing contact, the internal fillet radius of moving contact, the internal fillet radius of external end of dynamic and static contact, the radius of the outer corner of the two static side contacts and the opening distance of the grounding contact as the inputs, and takes the maximum electric field strength of the two static side contacts and the moving side contacts as outputs; Finally, the structural parameters are optimized by MOGOA algorithm. Compared to the pre‐optimization period, the electric field strengths of the bus bar static‐side contact, dynamic contact and static side contact of the B‐phase after optimization decreased from 20.2, 9.28 and 17.5 to 11.4, 6.65 and 11.5 kV/mm, respectively. The electric field strengths of the dynamic and static side contacts are significantly reduced, which is beneficial for improving the insulation performance of the three‐phase enclosed GIS disconnector. © 2023 Institute of Electrical Engineer of Japan and Wiley Periodicals LLC.

Publisher

Wiley

Subject

Electrical and Electronic Engineering

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3