Affiliation:
1. School of Electrical Engineering and Automation, Henan Key Laboratory of Intelligent Detection and Control of Coal Mine Equipment Henan Polytechnic University Jiaozuo China
Abstract
SummaryThe weighted average current (WAC) control method has gained recognition for its order reduction characteristics and broad control bandwidth. However, the interaction of digital control delay and grid impedance introduces an inverse resonance peak in the system loop gain, challenging the order reduction properties of conventional WAC control and system passivity across a wide frequency range. Conventional approaches, such as lead compensator‐based delay compensation or weighting coefficient redesign, improve system stability to some extent but fail to retain order reduction characteristics. To address these limitations, this article proposes a new control method known as weighted average mixed feedback, incorporating distinct voltage feedforward paths. By introducing a voltage feedback path, the proposed method reconfigures the system's zero positions, enabling the pole‐zero cancelation in the open‐loop characteristics independent of grid impedance. Additionally, this supplementary path offers impedance reshaping capabilities, enhancing system passivity and adaptability to weak grids. The effectiveness of the proposed control method is verified through simulations and experiments.
Funder
National Natural Science Foundation of China
Subject
Applied Mathematics,Electrical and Electronic Engineering,Computer Science Applications,Electronic, Optical and Magnetic Materials