Abstract
AbstractThis study utilized experimental research to investigate the efficiency of using normal aggregate concrete (NAC) or recycled aggregate concrete (RAC) as a new concrete layer for repairing projectile bullet damage to strengthening reinforced concrete (RC) beams. This study comprised the construction and testing of eight RC beams made of RAC and NAC. They are initially subjected to projectile bullets and after that tested with flexure load to evaluate the effect of using RAC and NAC that was investigated. The findings of test results demonstrate that the repaired specimens with RAC or NAC experienced a higher load capacity than the damaged control specimens. As such, this approach could potentially use to restore RAC or NAC beams were previously damaged by projectile bullets. In addition, the findings of this research indicate that the load capacity of the damaged RC beams that were previously repaired using the NAC layer was higher than the load capacity of the damaged RC beams that were repaired using the RAC layer. The load capacity enhanced significantly of (106%–118%) and (104%–113%), respectively, when NAC and RAC are utilized in repairs. Therefore, using either NAC or RAC concrete is more economical, environmentally friendly, and efficient than demolishing.