Measurements of electrical resistances and investigations of factors affecting corrosion and breakages of shielding layers in extruded three‐layer 6.6 kV XLPE cables

Author:

Kurihara Takashi1,Kimura Kenichi2,Watanabe Takuya2,Sato Tomoyuki2

Affiliation:

1. Central Research Institute of Electric Power Industry Nagasaka Japan

2. Tohoku Electric Power Network Co., Inc. Honcho Japan

Abstract

AbstractCorrosion and breakages of shielding layers are one of the factors for degradation of extruded three‐layer (E‐E type) 6.6 kV cross‐linked polyethylene (XLPE) cables. Tohoku Electric Power Network has been measuring electrical resistances of shielding layers in E‐E type 6.6 kV XLPE cables, and recently has found breakages of shielding layers. The authors performed an accelerated degradation test for shielding layers of E‐E type 6.6 kV XLPE cables by taking account of aqueous solution, temperature, heat cycles, bending stress, frequency of an applied voltage, and water‐proof layer in the test conditions, and investigated factors affecting corrosion and breakages of shielding layers. Corrosion, cracks, and breakages were found on shielding layers in the cables without water‐proof layer, but no crack was found in the cables with water‐proof layer, when heat cycles were applied to the cables, and shielding layers were supplied with artificial sea water. We investigated the suppressive effect of the cables with water‐proof layer on cracks and breakages of shielding layers by measuring tensile strengths of copper tapes obtained from the shielding layers of the cables with and without water‐proof layers.

Publisher

Wiley

Subject

Electrical and Electronic Engineering,Energy Engineering and Power Technology

Reference7 articles.

1. Insulation diagnosis technologies for electric power equipment;IEEE Japan Investigation R&D Committee on Insulation Diagnosis Technologies;Ohm‐sha,2015

2. Investigations of Effects of Cable Insulation Thickness and Water Immersion on AC Breakdown Voltage and Degradation Diagnostic Data and Possibility of Detection of Non-bridged Water Trees of Dry-cured and Extruded Three-layer (E-E Type) 6.6kV XLPE Cables

3. JCMA.Guidelines for Inspection and Maintenance of High‐voltage Cables.2012:116D(in Japanese)

4. Investigation of deterioration characteristics of 6.6 kV XLPE cables copper shielding tapes;Yoshida R;2019 National Convention Record IEE Japan,2019

5. Factors influencing corrosion (1);Akimov GV;Boshoku Gijutsu,1995

Cited by 1 articles. 订阅此论文施引文献 订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献

1. Comparison for Accelerated Degradation of New and Old 6.6 kV AC XLPE Cables;Journal of Electrical Engineering & Technology;2024-05-21