The impact of PV generation and load types on the impedance relays during both balanced and unbalanced faults

Author:

Kamel Rashad M., ,Abdullah Heba M.,

Abstract

Photovoltaic (PV) power generation and the types of connected loads both have an effect on protective impedance relays’ readings. This paper investigates this effect in a real distribution system installed in the State of Kuwait. It is found that, both the dynamic loads and the PV plants have considerable effects in the relay impedance value which vary according to the load type, PV connection and fault locationplace. Both single phase to ground fault (unsymmetrical fault) and three phase fault (symmetrical fault) are investigated. When single line to ground fault occurs at the PV bus (far from relay location), the dynamic loads increase the relay impedance while the PV plant decreases the relay impedance. When a single phase to ground fault occurs at the relay bus (load bus), the dynamic load decreases the relay impedance and the PV plant increases it. For a three-phase to ground fault at the relay bus, both dynamic load percentages and PV plant power generation have no effect on the protective relay impedance readings. At this condition, the relay impedance totally depends on the fault resistance. The main finding of this paper is that both the load type (especially dynamic load) and the PV plant have dominant effects on the protective impedance relay reading and setting. The distribution system planners and operators must consider the PV plant and types of load during designing, setting and adjusting the protective impedance relays. The most important point in this paper is considering real case study. This means that, the obtained results are more realistic than the assumed system in the other research. If the fault occurs at the location of the PV system’s bus when no PV power is generated, the dynamic load causes the relay impedance to increase, while connecting the PV decreases the relay impedance. The relay’s resistance and reactance increase from 0.3153Ω and 1.4950Ω, to 0.3456Ω and 1.6617Ω respectively when the dynamic load increases from 25% to 90% of the total load at constant high fault resistance. The relay resistance and reactance decrease from 0.2849Ω and 0.3443Ω (without PV plant), to 0.2195Ω and 0.3137Ω (with PV), respectively. When the dynamic load percentage increases from 25% to 90%, the resistance and reactance of the relay decrease from 1.0488Ω and 0.0051Ω, to 0.9526Ω and 0.0008Ω, respectively. This phenomenon is valid for all expected fault resistances. When considering constant dynamic load percentage and constant fault resistance, the relay resistance and reactance increase from 1.375Ω and 0.0022Ω (without PV) to 1.5745Ω and 0.0726 Ω (with PV), respectively. Based on those results, the impedance relay setting must be adjusted according to the percentage of the dynamic loads percentage, the PV penetration level, and the fault location.

Publisher

Journal of Engineering Research

Subject

General Engineering

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3